4100ES TrueAlert ES Addressable Appliance Field Checkout
Effective Date 09/01/2022
UPDATE DATE 10/26/2022
UPDATE DATE 11/07/2022
We have confirmed a reported issue with certain Autocall TrueAlert ES Addressable Notification Appliances, where they may not alarm visually and/or with sound after a period of regular operation of 11 months or longer. Some but not all Impacted Notification Appliances with speakers may then “chirp” (Tap Sense). Appliances with manufacturing date codes from 21 019 (Jan-19-2021) through 22 230 (Aug-18-2022) for xenon strobes and from 21 231 (Aug-19-2021) through 22 230 (Aug-18-2022) for LED strobes are impacted. Note – Speaker Only Appliances are not impacted.
The resolution will require the installation of a special version of EPS/IDNAC slave software for each EPS/IDNAC programmed in the system. The software will report a trouble for appliances which have failed. The Field Checkout and Repair Instructions will guide the technician through the process to verify whether appliances are working correctly or require replacement. Once completed, the system will be tested to conform to code requirements.
Note: Firmware version 2.01.02 or newer is required to remediate the IDNAC issue. Version 2.01.03 has been released and provides enhancements to the Self-Test feature but is not required to remediate the IDNAC issue. If a system has already been updated to version 2.01.02, it is not necessary to update to version 2.01.03 until the next normal service.
4100ES TrueAlert ES Addressable Notification Appliance Field Checkout
File Name |
Description |
---|---|
EPS FastFault Bin.Rev 3 File | FastFault version 3 of EPS Firmware – This file is only used to search for any affected notification devices and must be removed once the process has completed. See the instructions below for more details. UPDATED 9/27/2022 |
EPS Firmware Version 2.01.03 – This is the latest version of the EPS firmware as of 9/27/22 and this, or a newer version, MUST be installed after running FastFault version of the EPS firmware. | |
FastFault version 3 of ES-PS IDNAC Firmware – This file is only used to search for any affected notification devices and must be removed once the update process has completed. See the instructions below for more details. UPDATED 9/27/2022 | |
ES-PS IDNAC Firmware Version 2.01.03 – This is the latest version of the ES-PS IDNAC firmware as of 09/27/22 and this, or a newer version, MUST be installed after the FastFault version of the ES-PS IDNAC firmware has completed. |
|
Field Checkout and Repair Instructions explains the process on how to check Addressable Appliances to confirm normal operation, including how use of FastFault Firmware Version 6 UPDATED 11/07/2022 |